Gas Detection For Life

Personal monitors and fixed gas detectors

 

RKI banner
OX-500

Indoor Oxygen Diffusion Gas Monitor

DatasheetManual

OX-500 oxygen gas monitorRKI’s Model OX-500 is an indoor monitor that detects Oxygen (O2) levels with a range of 0-25% (0.1 vol% digit). It’s a sleek low profile design which lends itself to laboratory or commercial applications. The OX-500 comes ready to operate with a simple wall mount bracket and 10 foot power cord. If Oxygen level drops, the user is notified by an audible alarm tone and multicolored LED display.

The OX-500 uses a fast responding low-cost plug-in style galvanic cell sensor. This long life sensor is field-replaceable with no special tools required. An optional remote sensor is available in lengths of 3m, 5m, 10m, and 20m.

Features

  • Compact, wall mounting design
  • Highly visible 3 color LED digital display
  • Remote cable can enter from any direction
  • Stores alarm summary data
    (10 alarm occurrence, time and alarm concentration)

Applications

  • Prevent oxygen deficient accidents
  • Control oxygen levels
  • Laboratories
  • Warehouses
  • Tunnels
  • Clean room
  • Basements

Specifications

Model
OX-500
Measuring Gas
Oxygen (O2)
Sampling Method
Diffusion
Physical
Dimensions 95(W) x 135(H) x 35(D)mm
Weight
Approx. 420g (Approx. 220g in case of DC 24V version)
Display
3 digits, 3 color LED (Green, Orange, Red) Normal: Green
Mounting
Wall mounting type (by using accessory mounting plate or mount at one switch box) Cable inlet: Up, down and left/right, or rear side
Environmental
Operating Temp 0-40ºC (0 to 104ºF)
Relative
Humidity
below 95% RH (non-condensing)
Sensors
Sensor Types Galvanic Cell
Measuring
Ranges
0 ~ 25.0 vol% (0.1 vol% digit)
Outputs
Type of Alarms Gas alarm: 2 decrease alarms, latching mode (Non-latching with reset switch)
Trouble alarm: Self reset
Preset Alarm Levels 1st: 19.0 vol%, 2nd: 18.0 vol%
Relays Normally-open contact for both AL1/AL2, rated 125VAC to 1A (Resistive load)
Visual 1st Alarm: Flashing orange LED with gas display
AL1 LED orange color flashing, intermitted buzzer sound

2nd Alarm: Flashing red LED gas display
AL2 LED red color flashing, intermittent buzzer sound

Trouble Alarm: Red flashing display “E-**” (**shows error number), short intermittent buzzer sound
Power AC 100V 50/60Hz, Power consumption: Max 3.5VA, Power cable: 3m accessory (standard)

Option: (DC 24V, Power consumption: MAX 2.0)
Warranty One year materials and workmanship.

Oxygen deficiency and its reaction to human beings

O2 vol%
Symptoms
21%
Normal oxygen in air.
18%
Safety limit, needs ventilation.
12-16%
Strained breathing, high pulse, decrease of mental concentration, headache, ears ring, nausea.
9-14%
Fading consciousness, headache, nausea, pale complexion (cyanosis), slow reaction.
6-10%
Loses consciousness, cramps of the whole body
Below 6%
No consciousness, lethargy, stop breathing, heart rate stops, death within 6 minutes.

* Specifications subject to change without notice.